......@@ -23,6 +23,7 @@ modelica library to model fluid dynamic of HVAC systems
3-Enhancements
- FanVentilation: works with multi-species media
- The saturation pressure fonctions have been changed to work with a MoistAir bellow the triple point condition. It does not mean that the media can model a condensable moist air bellow the triple point conditions
- The orifices (except the compressible opening) can be initialised to a given velocity with a steady state condition. The flow regime can now be steady state or inertial.
- "SimpleOpening" and "VerticalOpening" are replaced by a signle "Opening" component. The bouyancy effect is no longer handled by dicretising the opening other the height but by analytical integration of hydrostatitque pressure other the height of the opening.
The opening (being an intrinsic vertical opening)
- The horizontal opening can handle buoyancy effect when density at the bottom is lower than than at the top
- All the openings can handle the altitude variation between opening and boundary nodes